求英文翻译

Air/Vapor Treatment at Junctions
Air and vapor leakage at wall/roof junctions is perhaps the predominant
construction problem in cold storage facilities.
When a cold room of interior/exterior design is
lowered to operating temperature, the structural elements contract and can pull the roof away from the wall.
Negative pressure in the space of the wall/roof junction can cause
warm, moist air to leak into the room and form frost and ice. Therefore,
proper design and construction of the air/vapor seal is critical.
An air/vapor flashing sheet system (a transition from the roof
vapor retarder to the exterior wall vapor retarder) is best for preventing
leakage. A good corner flashing sheet must be flexible, tough,
airtight, and vaportight. Proper use of flexible insulation at overlaps,
mastic adhesive, and a good mastic sealer ensure leak-free performance.
To remain airtight and vaportight during the life of the facility,
a properly constructed vapor retarder should
1.Be flexible enough to withstand building movements that may
occur at operating temperatures
2.Allow for thermal contraction of the insulation as the room is
pulled down to operating temperature
3.Be constructed with a minimum of penetrations that might cause
leaks (wall ties and structural steel that extend through the corner
flashing sheet may eventually leak no matter how well sealed during
construction; minimize these, and make them accessible for
maintenance)
4.Have corner flashing sheet properly lapped and sealed with adhesive
and mechanically fastened to the wall vapor retarder
5.Have corner flashing sealed to roof without openings
6.Have floor to exterior vapor retarders that are totally sealed
The interior/exterior design is likely to be unsuccessful
at the wall/roof junction because of extreme difficulty in
maintaining an airtight or vaportight environment.
The practices outlined for the wall/roof junction apply for other
insulation junctions. The insulation manufacturer and designer must
coordinate details of the corner flashing design.
Poor design and shoddy installation cause moist air leakage into
the facility, resulting in frost and ice formation, energy loss, poor
appearance, loss of useful storage space, and, eventually, expensive
repairs.
Floor Construction
Refrigerated facilities held above freezing need no special
underfloor treatment. A below-the-floor vapor retarder is needed
in facilities held below freezing, however. Without underfloor
heating, the subsoil eventually freezes; any moisture in this soil
also freezes and causes floor frost heaving. In warmer climates,
underfloor tubes vented to ambient air may be sufficient to prevent
heaving.

Air/Vapor Treatment at Junctions

空气/蒸汽处理结点处

Air and vapor leakage at wall/roof junctions is perhaps the predominant

空气和水蒸气泄漏墙体/屋顶路口也许是最主要的

construction problem in cold storage facilities.

在冷储藏设施建设问题。

When a cold room of interior/exterior design is

当一间冰冷的屋子内外设计的

lowered to operating temperature, the structural elements contract and can pull the roof away from the wall.

操作温度,降低了结构元素合同和屋顶能拉离墙。

Negative pressure in the space of the wall/roof junction can cause

负压的空间里墙上/顶板交接处的原因

warm, moist air to leak into the room and form frost and ice. Therefore,

温暖、潮湿的空气泄漏进房间,形成霜和冰。因此,

proper design and construction of the air/vapor seal is critical.

正确的设计和施工的空气/气体密封是至关重要的。

An air/vapor flashing sheet system (a transition from the roof

一种空气/蒸汽闪烁的组卷系统(转换屋顶

vapor retarder to the exterior wall vapor retarder) is best for preventing

蒸汽缓凝剂的缓凝剂的外墙蒸汽)是最好的预防

leakage. A good corner flashing sheet must be flexible, tough,

泄漏。一个好的角闪烁的单必须是灵活的,不幸的,

airtight, and vaportight. Proper use of flexible insulation at overlaps,

密闭,vaportight。正确使用灵活,在重叠绝缘

mastic adhesive, and a good mastic sealer ensure leak-free performance.

乳香胶粘剂生产企业,以及一个良好的乳香封口机确保问题保持注射的性能。

To remain airtight and vaportight during the life of the facility,

保持密闭而vaportight生活中这个设施,

a properly constructed vapor retarder should

一个适当建造蒸汽缓速器应该

1. Be flexible enough to withstand building movements that may

1。是灵活的,足以抵挡建筑动作,五月

occur at operating temperatures

发生在操作温度

2. Allow for thermal contraction of the insulation as the room is

2。允许热收缩的房间是绝缘的

pulled down to operating temperature

拉下来的工作温度

3. Be constructed with a minimum of penetrations that might cause

3。构建以最小的穿透这可能引起

leaks (wall ties and structural steel that extend through the corner

漏钢结构(墙伸展的关系,通过角球

flashing sheet may eventually leak no matter how well sealed during

闪烁的单可能最终不管多好密封泄漏的期间

construction; minimize these, and make them accessible for

建设;减小这种,使他们可以接近的

maintenance)

维修)

4. Have corner flashing sheet properly lapped and sealed with adhesive

4。有角闪烁板妥善研磨和密封胶

and mechanically fastened to the wall vapor retarder

和刚性固定在墙上蒸汽缓速器

5. Have corner flashing sealed to roof without openings

5。屋顶上有角闪烁的密封,并没有开口

6. Have floor to exterior vapor retarders that are totally sealed

6。有地板,外部水蒸气缓完全密封

The interior/exterior design is likely to be unsuccessful

室内/外观设计很可能是不成功的

at the wall/roof junction because of extreme difficulty in

在墙上/顶板交接处,因为极端困难的

maintaining an airtight or vaportight environment.

维持密闭或vaportight环境。

The practices outlined for the wall/roof junction apply for other

概述了实践的墙/屋顶交界处申请其他

insulation junctions. The insulation manufacturer and designer must

绝缘过程。绝缘制造商和设计师必须

coordinate details of the corner flashing design.

闪烁细节墙角的协调设计。

Poor design and shoddy installation cause moist air leakage into

设计不良伪劣安装造成潮湿的空气泄漏到

the facility, resulting in frost and ice formation, energy loss, poor

这个设施,造成冰霜和冰的形成、能量损失,贫穷

appearance, loss of useful storage space, and, eventually, expensive

外观,损失的有用的储藏空间,和最终的,昂贵的

repairs.

修理。

Floor Construction

地坪施工

Refrigerated facilities held above freezing need no special

冷藏设施不需要特别举行了冰点

underfloor treatment. A below-the-floor vapor retarder is needed

地下的治疗。一个below-the-floor蒸汽缓速器是需要的

in facilities held below freezing, however. Without underfloor

在零度以下设施,但举行。没有地下

heating, the subsoil eventually freezes; any moisture in this soil

加热,例举任何水分结冰,最终在这块土地

also freezes and causes floor frost heaving. In warmer climates,

地板也冻结和冻胀引起的。在温暖的气候中,

underfloor tubes vented to ambient air may be sufficient to prevent

发泄周围空气对地下管可能是必要的预防措施

heaving.

胀。
温馨提示:内容为网友见解,仅供参考
第1个回答  2011-03-28
有的词可能打错了哟!

空气/蒸汽处理结点处

空气和水蒸气泄漏墙体/屋顶路口也许是最主要的

在冷储藏设施建设问题。

当一间冰冷的屋子内外设计的

操作温度,降低了结构元素合同和屋顶能拉离墙。

负压的空间里墙上/顶板交接处的原因

温暖、潮湿的空气泄漏进房间,形成霜和冰。因此,

正确的设计和施工的空气/气体密封是至关重要的。

一种空气/蒸汽闪烁的组卷系统(转换屋顶

蒸汽缓凝剂的缓凝剂的外墙蒸汽)是最好的预防

泄漏。一个好的角闪烁的单必须是灵活的,不幸的,

密闭,vaportight。正确使用灵活,在重叠绝缘

乳香胶粘剂生产企业,以及一个良好的乳香封口机确保问题保持注射的性能。

保持密闭而vaportight生活中这个设施,

一个适当建造蒸汽缓速器应该

1。是灵活的,足以抵挡建筑动作,五月

发生在操作温度

2。允许热收缩的房间是绝缘的

拉下来的工作温度

3。构建以最小的穿透这可能引起

漏钢结构(墙伸展的关系,通过角球

闪烁的单可能最终不管多好密封泄漏的期间

建设;减小这种,使他们可以接近的

维修)

4。有角闪烁板妥善研磨和密封胶

和刚性固定在墙上蒸汽缓速器

5。屋顶上有角闪烁的密封,并没有开口

6。有地板,外部水蒸气缓完全密封

室内/外观设计很可能是不成功的

在墙上/顶板交接处,因为极端困难的

维持密闭或vaportight环境。

概述了实践的墙/屋顶交界处申请其他

绝缘过程。绝缘制造商和设计师必须

闪烁细节墙角的协调设计。

设计不良伪劣安装造成潮湿的空气泄漏到

这个设施,造成冰霜和冰的形成、能量损失,贫穷

外观,损失的有用的储藏空间,和最终的,昂贵的

修理。

地坪施工

冷藏设施不需要特别举行了冰点

地下的治疗。一个below-the-floor蒸汽缓速器是需要的

在零度以下设施,但举行。没有地下

加热,例举任何水分结冰,最终在这块土地

地板也冻结和冻胀引起的。在温暖的气候中,

发泄周围空气对地下管可能是必要的预防措施

胀。
第2个回答  2011-03-28
空气/蒸汽处理结点处
空气和水蒸气泄漏墙体/屋顶路口也许是最主要的
在冷储藏设施建设问题。
当一间冰冷的屋子内外设计的
操作温度,降低了结构元素合同和屋顶能拉离墙。
负压的空间里墙上/顶板交接处的原因
温暖、潮湿的空气泄漏进房间,形成霜和冰。因此,
正确的设计和施工的空气/气体密封是至关重要的。
一种空气/蒸汽闪烁的组卷系统(转换屋顶
蒸汽缓凝剂的缓凝剂的外墙蒸汽)是最好的预防
泄漏。一个好的角闪烁的单必须是灵活的,不幸的,
密闭密室。 正确使用灵活,在重叠绝缘
乳香胶粘剂生产企业,以及一个良好的乳香封口机确保问题保持注射的性能。
保持密闭而密室t生活中这个设施,
一个适当建造蒸汽缓速器应该
1。是灵活的,足以抵挡建筑动作,五月
发生在操作温度
2。允许热收缩的房间是绝缘的
拉下来的工作温度
3。构建以最小的穿透这可能引起
漏钢结构(墙伸展的关系,通过角球
闪烁的单可能最终不管多好密封泄漏的期间
建设;减小这种,使他们可以接近的
维修)
4。有角闪烁板妥善研磨和密封胶
和刚性固定在墙上蒸汽缓速器
5。屋顶上有角闪烁的密封,并没有开口
6。有地板,外部水蒸气缓完全密封
室内/外观设计很可能是不成功的
在墙上/顶板交接处,因为极端困难的
维持密闭或密室环境。
概述了实践的墙/屋顶交界处申请其他
绝缘过程。绝缘制造商和设计师必须
完整。
相似回答